Basic Info
  • Model NO.: FT6-12
  • Structure: Three-column Disconnector
  • Operation: Manual
  • Movement Mode: Vertical Rotary Type
  • Grounding: Single Ground
  • Run: Plug-In
  • Common Model: FT6-12
  • Certification: ISO, IS9001, ISO9001, ISO9002
  • Rated volatge: 12 KV
  • Rated short-circuit current: 31.5 KA
  • Trademark: Tianan Electric
  • Type: High-voltage
  • Installation: Indoor High-voltage
  • Grounding Mode: Grounding
  • Number of Poles: Three Pole
  • Series: Three
  • Switching Mode: Single Throw-in
  • Structure of Operating: Manual
  • Brand: Tianan Electric
  • Rated current: 630 A
  • Types: FT6-12
  • Specification: IEC
Product Description
FT6-12 Series Outdoor AC high voltage vacuum load switch
 
1. Product Description
        FT6-12 / T630 Outdoor AC high voltage vacuum isolation load switch for outdoor three-phase AC 50Hz, rated voltage 12KV outdoor distribution system as breaking and closing load current purposes, can also be used as breaking and closing no-load circuit, no-load transformer current purposes. Meet the outdoor all-weather operating conditions, corrosion resistant, anti-contamination features.
        The vacuum load switch designed and developed by our company is made. The product is compact, small size, light weight, interrupter independent structure to ensure that the process of breaking free from outside influence operations, breaking current, arcing safe and reliable; obviously isolated fracture; equipped with a special operation actuator, can be manual or electric dual operation; product basic maintenance; the load switch can be upgraded to smart load switch for distribution automation, also be equipped with a vacuum controller is upgraded to automatic slicer.
 
2. Structural features:
        This switch mainly by the interrupter, isolating switch, actuator and other components. Isolation switch structure vertical rotation mode, there is no natural hazards close down, up and down through the insulator is fixed to the base frame. Interrupter by the excellent performance of vacuum tubes and manual rapid grouped brake mechanism. Fixed disconnector fixed contact side. Actuator mounted on the right inside the chassis, connected by a rod and spindle isolation switch.
 
3. Type meaning
F T 6 - 12 / T 630 -16
F: AC high voltage load switch
T: Enterprise Code
6: Reference Design
12: Rated voltage
T: spring energy
630: Rated current (A)
16: rated short time withstand current kA
 
4. The main technical parameters
No.ItemUnitParameters
1Rated voltagekV12
2Rated frequencyHz50
3Rated currentA630
4Rated active load breaking currentA630
5Rated breaking current loopA630
65% rated active load breaking currentA31.5
7Rated cable charging breaking currentA10
8Rated short time withstand currentkA/s16/4
9Rated capacitor breaking currentA400
10Rated no-load transformer breaking current
6000kVA
Transformer no-load current
11Rated peak withstand current (dynamic stability)kA40
12Rated short-circuit current (thermal stability)kA40
131min power frequency withstand voltage (rms) to ground, interphase / isolation fracturekV42/48
14Lightning impulse withstand voltage (peak) to ground, interphase / isolation fracturekV75/85
151 min wet withstand voltage to ground, interphase / isolation fracturekV34
16Interrupter fracture 1min power frequency withstand voltagekV20
17Mechanical life
2000
 
 
5. Actuator Technical Data
No.ItemRatingsThe normal operating range
1Closing motorTated voltage DC/AC 220V Rating: 50W85% ~ 110% Reliable closing
2Tripping coilTated voltage  AC 220V,current 3A65% ~ 120% Reliable opening
 
6. The switching process consists of two parts
- Switch compact, small size, light weight, simple and reliable mechanism, easy to operate;
- Can be manually operated and electric operation.
 
7. Ordering Information
a, load switch model, name, number, manual or electric operation (operating power)
b, load switch installation outdoors, columns Size and installation requirements to provide the necessary accessories
 